All about water...

Reverse Osmosis Boiler Feed Water
  • 2026-05-09

Reverse Osmosis Boiler Feed Water

The efficient operation of the boiler system depends on strict feed water quality control. The pretreatment system needs to remove the following pollutants in a targeted manner:Scaling factors: calcium/magnesium hardness ions, silica (need to be contr…

The efficient operation of the boiler system depends on strict feed water quality control. The pretreatment system needs to remove the following pollutants in a targeted manner:

Scaling factors: calcium/magnesium hardness ions, silica (need to be controlled ≤0.02ppm), aluminum and iron-manganese metal ions

Corrosion factors: dissolved oxygen, carbon dioxide and copper ions (risk of high-pressure turbine deposition)

System damage factors: suspended solids, organic matter and abnormal alkalinity

Limitations of traditional water treatment processes

Sole reliance on ion exchange or chemical dosing has inherent defects:

Water softeners cannot remove silica and TDS

Frequent regeneration leads to a sharp increase in acid and alkali consumption

Water quality fluctuations aggravate condensation system corrosion

RO pretreatment system solution

Using reverse osmosis as the core process can simultaneously achieve:

Process optimization

Configure RO system before desalination device to reduce regeneration frequency and reagent consumption by 60%

Replace traditional water softener to eliminate steam contamination risk caused by alkalinity fluctuation

Engineering specification

Use ASME certified pressure vessel

Configure online water quality monitoring (conductivity/pH/ORP)

Modular design adapts to 5-500m³/h treatment scale

Improve economic benefits of the whole system

Reduced energy consumption: Clean heat transfer surface to improve thermal efficiency, reduce fuel cost per ton of steam by 15%

Maintenance optimization: scale inhibition rate ≥ 95% to extend furnace cleaning cycle, shorten annual downtime by 40%

Chemical emission reduction: reduce the amount of scale inhibitor/neutralizer by 50%

Life extension: control feed water pH 8.5-9.5, the service life of key equipment is increased by 3-5 years

Key indicators for water quality control

Control parameters Target range Mechanism of action

Dissolved oxygen ≤0.007ppm Inhibit oxygen corrosion

Total iron ≤0.01ppm Prevent corrosion under sediments

Silicon dioxide ≤0.02ppm Eliminate silicate scaling

Alkalinity Maintain buffer capacity Control the corrosion rate of the condensation system


Copyright © 2026 fupengwater.com Corporation,All Rights Reserved. Hebei Fupeng Environmental Protection Technology Group Co., LTD